HBD-D5015A® energy storage system primarily adopts a highly integrated design, incorporating battery clusters, distribution cabinets, liquid cooling units.and fire protection systems all installed within a 20-foot container for ease of transportation.
The system features independent power supply, cooling, and fire protection systems

HBD-D5015A® energy storage system primarily adopts a highly integrated design, incorporating battery clusters, distribution cabinets, liquid cooling units.and fire protection systems all installed within a 20-foot container for ease of transportation. The system features independent power supply, cooling, and fire protection systems.
HBD® is mainly developed for no emission and low noise, Reduce the dependence on grid, Improve power supply quality and Ensure the power consumption of emergency load.
High Density: 5.015MWh in a standard 20ft container (using 314Ah cells), maximizing space efficiency for shipping.
High Safety: Triple-level (PACK, cluster, cabin) fire protection; multi-level fusing; IP67-rated battery packs.
High Efficiency: Smart thermal management; real-time remote monitoring and early warning for reliable operation.

| General Information | |
|---|---|
| Rated Battery Storage Capacity | 5015 kWh |
| Battery Stack | 12*1P416S |
| Rated Voltage | 1331.2VDC |
| DC Voltage Range | 1164.8VDC~1497.6VDC |
| Charge/Discharge Rate | 0.5P |
| Protection Class | IP55 |
| Loading Dimension | 2438mm*6058mm*2896mm(ISO 20’HQ) |
| Net.Weight | 45000 kg |
| Loading Capacity | 1 units |
| Discharge Temperature Range | -20~55°C(> 45 ℃ derating) |
| Humidity | 0~95%(No Condensation) |
| Max Altitude | ≤ 3000m (> 2000m derating) |

| Battery | |
|---|---|
| Cell Type | LFP(LiFePO₄) |
| Cell Capacity | 314Ah |
| Pack Capacity | 104.5 kWh |
| Pack Rated Voltage | 332.8 VDC |
| System Configuration Mode | 12*(1P104S*4) |
| Rack Capacity | 417.99 kWh |
| Battery Voltage of Rack | 1164.8~1497.6VDC |
| Rack Rated Voltage | 1331.2VDC |
| Cyclic Life | 8000 Times(0.5C@80%DOD) |
| Max. Charge/Discharge Rate | 0.5P |
| Cooling System | |
| Battery Cabin | Active Liquid Cooling |
| Coolant | 50% ethylene glycol solution |
| Protection Device | |
| Fire Suppressant | Aerosol system(pack level and container level), water spray system , explosion-proof ventilation |
| Sensor | Smoke detector, temperature detector , Flammable Gas detector , Fire sound and light alarm |
| Auxiliary Power | |
| Auxiliary Power | UPS ( AC400V, 50Hz ) |
| Other | |
| Communication Interface | Ethernet/RS485/CAN |
| Certification | |
| Certification | IEC62477, IEC61000, IEC62619, IEC63056, UL9540A, UN3536 |